Segment 1
*****************************************************************************
BESCHREIBUNG :
---------------
Dieser Baustein setzt das PLI ( Phase Logic Interface ) von Open - Batch
auf die Schnittstelle HsH - PC zur SPS - Waage ( DB 210 ) um
******************************************************************************
PARAMETER :
-----------
PLDX : Nr. des DX Datenbaustein fuer PLI
OFFS : Offset fuer PLI Anfang
WZNR : Zaehlnummer der SPS - Waage
DBPC : Datenbaustein fuer Schnittstelle PC - SPS Waage
DBST : Steuerdatenbaustein PC - SPS Waage
AUTO : Automatik - Mode
******************************************************************************
Name :PL-SS-EM
Decl :PLDX I/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF
Decl :OFFS I/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF
Decl :WZNR I/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF
Decl :EMPY I/Q/D/B/T/C: I BI/BY/W/D: BI
Decl :UNID I/Q/D/B/T/C: I BI/BY/W/D: BI
Decl :TDDP I/Q/D/B/T/C: T
:***
Segment 2 PLI DX oeffnen
:LW =PLDX
:T -MW188 ADDR_OBJECT_DB/DX
:DO -MW188 ADDR_OBJECT_DB/DX
:CX -DX 0 SYSTEM PARAMETER
:***
FW 188 = MW188 ADDR_OBJECT_DB/DX
DX 0 = DX 0 SYSTEM PARAMETER
Segment 3 Load Control bits PLI
:LW =OFFS
:L KF +10
:+F
:T -MW186 DW_ADDRESS
:DO -MW186 DW_ADDRESS
:L DW 0
:T -MW 168_OUT_PLI Ausgangsbitleiste von PLI
: --------------------------------
:L -MW186 DW_ADDRESS
:L KF +1
:+F
:T -MW186 DW_ADDRESS 11
:DO -MW186 DW_ADDRESS
:L DW 0
:T -MW 166_IN_PLI Eingangsbitleiste von PLI
: --------------------------------
:***
FW 186 = MW186 DW_ADDRESS
FW 168 = MW 168_OUT_PLI Ausgangssteuerbitleiste von PLI
FW 166 = MW 166_IN_PLI Eingangsbitleiste an PLI
Segment 4 Load Status bits PLI / Unit idle
:LW =OFFS
:L KF +19
:+F
:T -MW186 DW_ADDRESS
:DO -MW186 DW_ADDRESS
:L DW 0
:T -MW 160_STATUS_PL Status bits PLI
: --------------------------------
:JU =M001 !!!!!!!!!!!!! TEST !!!!!!!!!!!!!
:A -MO169.4 START_BY_PLI
:AN =UNID
:R -MO169.4 START_BY_PLI
:S -MI167.4 IDLE(ready)
M001 :***
FW 186 = MW186 DW_ADDRESS
FW 160 = MW 160_STATUS_PL
F 169.4 = MO169.4 START_BY_PLI
F 167.4 = MI167.4 IDLE(ready)
Segment 5 Request registers
:LW =OFFS
:T -MW 152 PHASE_REQUEST
:
:L -MW 152 PHASE_REQUEST
:I 13
:T -MW 154 REQ_DATA1
:
:L -MW 152 PHASE_REQUEST
:I 14
:T -MW 156 REQ_DATA2
:
:L -MW 152 PHASE_REQUEST
:I 12
:T -MW 158 PHASE_ST_FAILURE
:
:L KF +0
:DO -MW 158 PHASE_ST_FAILURE
:T DW 0 reset stored failure
:***
FW 152 = MW 152 PHASE_REQUEST
FW 154 = MW 154 REQ_DATA1
FW 156 = MW 156 REQ_DATA2
FW 158 = MW 158 PHASE_ST_FAILURE
Segment 6 Operator confirm
:DO -MW 152 PHASE_REQUEST
:L DW 0
:L KF +1200
:>=F
:= -MS161.4 ! OPER_CONFRM !
:***
FW 152 = MW 152 PHASE_REQUEST
F 161.4 = MS161.4 ! OPER_CONFRM !
Segment 7 Request in work
:DO -MW 152 PHASE_REQUEST
:L DW 0
:L KF +6000
:!=F
:= F 200.0 RQ 6000
:R -MI167.6 RQ_IN_WORK
:DO -MW 152 PHASE_REQUEST
:L DW 0
:L KF +1000
:>=F
:AN F 200.0 RQ 6000
:S -MI167.6 RQ_IN_WORK
:JC =M001
:
:L KF +0
:DO -MW 154 REQ_DATA1
:T DW 0
:DO -MW 156 REQ_DATA2
:T DW 0
M001 :***
FW 152 = MW 152 PHASE_REQUEST
F 167.6 = MI167.6 RQ_IN_WORK
FW 154 = MW 154 REQ_DATA1
FW 156 = MW 156 REQ_DATA2
Segment 8 Complete
:L -MW 152 PHASE_REQUEST
:L KF +4
:+F
:T -MW186 DW_ADDRESS
:DO -MW186 DW_ADDRESS
:L DW 0
:L KF +70
:!=F
:S -MI167.1 COMPLETE
:
:AN -MO169.4 START_BY_PLI
:JC =M001
:
:AN -M 0.1 CONSTANT 1
:SD =TDDP
M001 :***
FW 152 = MW 152 PHASE_REQUEST
FW 186 = MW186 DW_ADDRESS
F 167.1 = MI167.1 COMPLETE
F 169.4 = MO169.4 START_BY_PLI
F 0.1 = M 0.1 CONSTANT 1
Segment 9 start sequence
:L -MW 152 PHASE_REQUEST
:L KF +3
:+F
:T -MW186 DW_ADDRESS
:DO -MW186 DW_ADDRESS
:L DW 0
:T -MW 150 PHASE_STEP_INDEX
:
:AN -MO169.4 START_BY_PLI
:AN F 200.0 RQ 6000
:JC =M001
:
:L KF +0
:T -MW 160_STATUS_PL
:
:AN -MO169.4 START_BY_PLI
:JC =M001
:L KF +30
:T -MW 150 PHASE_STEP_INDEX
M001 :***
FW 152 = MW 152 PHASE_REQUEST
FW 186 = MW186 DW_ADDRESS
FW 150 = MW 150 PHASE_STEP_INDEX
F 169.4 = MO169.4 START_BY_PLI
FW 160 = MW 160_STATUS_PL
Segment 10 Step 10: load para
:***
FW 150 = MW 150 PHASE_STEP_INDEX
F 167.5 = MI167.5 PLI_RUNNING
F 167.6 = MI167.6 RQ_IN_WORK
F 160.0 = MS160.0 STP 10: ACTIVE
FW 154 = MW 154 REQ_DATA1
FW 156 = MW 156 REQ_DATA2
F 0.1 = M 0.1 CONSTANT 1
FW 152 = MW 152 PHASE_REQUEST
F 166.0 = MI166.0 RQ_1100 DLpart
F 161.7 = MS161.7 STP 10:HOLD_ACT
FW 158 = MW 158 PHASE_ST_FAILURE
Segment 11 Step 20: confirm empty or overri
:***
FW 150 = MW 150 PHASE_STEP_INDEX
F 167.5 = MI167.5 PLI_RUNNING
F 167.6 = MI167.6 RQ_IN_WORK
F 160.1 = MS160.1 STP 20: ACTIVE
FW 152 = MW 152 PHASE_REQUEST
F 166.0 = MI166.0 RQ_1100 DLpart
F 0.1 = M 0.1 CONSTANT 1
Segment 12 Step 30: Upload reports
:L -MW 150 PHASE_STEP_INDEX
:L KF +30
:><F
:ON -MI167.5 PLI_RUNNING
:O -MI167.6 RQ_IN_WORK
:JC =M001
:AN -MS160.2 STP 30: ACTIVE
:S -MS160.2 STP 30: ACTIVE
:JC =M001
M002 :R -MS160.2 STP 30: ACTIVE
M001 :***
FW 150 = MW 150 PHASE_STEP_INDEX
F 167.5 = MI167.5 PLI_RUNNING
F 167.6 = MI167.6 RQ_IN_WORK
F 160.2 = MS160.2 STP 30: ACTIVE
FW 152 = MW 152 PHASE_REQUEST
FW 158 = MW 158 PHASE_ST_FAILURE
F 0.1 = M 0.1 CONSTANT 1
Segment 13 Control bits PLI
:A =UNID
:= -MS161.5 !! UNIT IDLE !!
:
:A -MO169.4 START_BY_PLI
:AN -MO169.0 ABORTING_BY_PLI
:AN -MO169.2 STOPPING_BY_PLI
:S -MI167.5 PLI_RUNNING
:
:A -MO169.0 ABORTING_BY_PLI
:S -MI167.3 ABORTED
:
:A -MO169.1 HOLDING_BY_PLI
:S -MI167.0 HELD
:
:A -MO169.3 RESTART_BY_PLI
:S -MI166.3 RESTART_COMPL
:***
F 161.5 = MS161.5 !! UNIT IDLE !!
F 169.4 = MO169.4 START_BY_PLI
F 169.0 = MO169.0 ABORTING_BY_PLI
F 169.2 = MO169.2 STOPPING_BY_PLI
F 167.5 = MI167.5 PLI_RUNNING
F 167.3 = MI167.3 ABORTED
F 169.1 = MO169.1 HOLDING_BY_PLI
F 167.0 = MI167.0 HELD
F 169.3 = MO169.3 RESTART_BY_PLI
F 166.3 = MI166.3 RESTART_COMPL
Segment 14 Control bits PLI
:A -MO169.2 STOPPING_BY_PLI
:AN -MI167.6 RQ_IN_WORK
:AN -MI167.2 STOPPED
:S -MI167.2 STOPPED
:
:O -MO169.0 ABORTING_BY_PLI
:O -MO169.2 STOPPING_BY_PLI
:R -MS160.2 STP 30: ACTIVE
:
:A -MI167.5 PLI_RUNNING
:A -MS160.2 STP 30: ACTIVE
:S -MI167.1 COMPLETE
:O -MO169.0 ABORTING_BY_PLI
:O -MO169.1 HOLDING_BY_PLI om 169.1
:O -MO169.2 STOPPING_BY_PLI
:O -MO169.4 START_BY_PLI
:R -MI167.1 COMPLETE
:***
F 169.2 = MO169.2 STOPPING_BY_PLI
F 167.6 = MI167.6 RQ_IN_WORK
F 167.2 = MI167.2 STOPPED
F 169.0 = MO169.0 ABORTING_BY_PLI
F 160.2 = MS160.2 STP 30: ACTIVE
F 167.5 = MI167.5 PLI_RUNNING
F 167.1 = MI167.1 COMPLETE
F 169.1 = MO169.1 HOLDING_BY_PLI
F 169.4 = MO169.4 START_BY_PLI
Segment 15 PLI DX
:LW =PLDX
:T -MW188 ADDR_OBJECT_DB/DX
:DO -MW188 ADDR_OBJECT_DB/DX
:CX -DX 0 SYSTEM PARAMETER
:***
FW 188 = MW188 ADDR_OBJECT_DB/DX
DX 0 = DX 0 SYSTEM PARAMETER
Segment 16 Store step number
:LW =OFFS
:L KF +3
:+F
:T -MW186 DW_ADDRESS
:
:L -MW 150 PHASE_STEP_INDEX
:DO -MW186 DW_ADDRESS
:T DW 0
:***
FW 186 = MW186 DW_ADDRESS
FW 150 = MW 150 PHASE_STEP_INDEX
Segment 17 Store Control bits PLI
:LW =OFFS
:L KF +11
:+F
:T -MW186 DW_ADDRESS
:
:L -MW 166_IN_PLI
:DO -MW186 DW_ADDRESS
:T DW 0
:
:LW =OFFS
:L KF +19
:+F
:T -MW186 DW_ADDRESS
:
:L -MW 160_STATUS_PL
:DO -MW186 DW_ADDRESS
:T DW 0
:***
FW 186 = MW186 DW_ADDRESS
FW 166 = MW 166_IN_PLI Eingangsbitleiste an PLI
FW 160 = MW 160_STATUS_PL
Segment 18 Reports to PLI
:LW =WZNR
:L KF +100
:+F
:T FW 190
:
:L KF +198
:T FW 192
:
:L KF +38
:T FW 194
:
:L KF +2
:T FW 196
:***
Segment 19 Record report
:AN -MI167.5 PLI_RUNNING
:R -MS160.2 STP 30: ACTIVE
:
:O -MS160.2 STP 30: ACTIVE
:O -MO169.2 STOPPING_BY_PLI
:AN -MI167.6 RQ_IN_WORK
:JC -FB173 COPY BLOCK
Name :COPY DKF
QUEL : KS DB DB
DB-Q : FW 190 10X
VON : FW 192 198
BIS : FW 192
ZIEL : KS DB DB
DB-Z : FW 190 10X
NACH : FW 194 38
FEHL : -M 0.0 IND.ADDRES(DUMMY)
LAEN : FW 196 2 DW's
L-B : KS LA
:***
F 167.5 = MI167.5 PLI_RUNNING
F 160.2 = MS160.2 STP 30: ACTIVE
F 169.2 = MO169.2 STOPPING_BY_PLI
F 167.6 = MI167.6 RQ_IN_WORK
F 0.0 = M 0.0 IND.ADDRES(DUMMY)
FB 173 = FB173 COPY BLOCK parameter: EW sp
Segment 20 Reports to PLI
:L -MW 152 PHASE_REQUEST
:L KF +44
:+F
:T FW 198
:O -MS160.2 STP 30: ACTIVE
:O -MO169.2 STOPPING_BY_PLI
:AN -MI167.6 RQ_IN_WORK
:JC -FB173 COPY BLOCK
Name :COPY DKF
QUEL : KS DB DB
DB-Q : FW 190 10X
VON : FW 192 198
BIS : FW 192
ZIEL : KS DX DX
DB-Z : -MW188 ADDR_OBJECT_DB/DX
NACH : FW 198 44
FEHL : -M 0.0 IND.ADDRES(DUMMY)
LAEN : FW 196 2 DW's
L-B : KS LA
:BE
FW 152 = MW 152 PHASE_REQUEST
F 160.2 = MS160.2 STP 30: ACTIVE
F 169.2 = MO169.2 STOPPING_BY_PLI
F 167.6 = MI167.6 RQ_IN_WORK
FW 188 = MW188 ADDR_OBJECT_DB/DX
F 0.0 = M 0.0 IND.ADDRES(DUMMY)
FB 173 = FB173 COPY BLOCK parameter: EW sp