# TA522_CHARGE implemented in DK PLC program file 18 ## aborting | |RQ |Q01|Q02| F |---|-----|---|---|---| |0 | |10 | | | | | complete ## holding | |RQ |Q01|Q02| F |---|-----|---|---|---| |0 | |10 | | | | | complete ## stopping | |RQ |Q01|Q02| F |---|-----|---|---|---| |0 | |10 |2000 | | | | upload reports |20 | | | | | complete ## restarting | |RQ |Q01|Q02| F |---|-----|---|---|---| |0 | | | | | if SB = 41,42 or 43 set it to 40 |10 | | | | | complete ## running | |RQ |Q01|Q02| F |---|-----|---|---|---| |0 |1106 | 3 | 3 | | download parameters |10 | | | | 1 | hold at start (if required) |20 |5201 | | | | wait for partner |30 |1201 | | | | confirm to start (if required) |40 | | | | | compute target 1 and reset timers |41 | | | | | await target 1 reached |42 | | | | | calc target 2 |43 | | | | | await target 2 reached |44 | | | | | air valve |45 | | | | | goto 40 if more of 50 if done |50 | | | | | 60 if pwork confirm else 90 (there never is!) |60 |1203 | | | | pipework confirm (non existent!) |60 |1203 | | | | pipework confirm (non existent!) |70 | | 80|1202 | | | | confirm complete if required then 100 | 90|1202 | | | | confirm complete if required then 100 |100|5202 | | | | await message partner |110| |120| | | | 2 | hold at end (if required) |130|2000 | | | | upload all reports