batch-example-2/document/equipment-modules/TA521_STIR.md

4.2 KiB

TA521_STIR

equipment module

unit: TA521

recipe phase: STIR

property value
UniqueName TA521_STIR
RecipePhase STIR
EquipmentPhaseType TAGPHASE
UniqueID 213
MaxOwners 1
UploadDownloadFlags 1793
CreateParameterLimitTag false
CreateReportLimitTag false
OnControlScanRate 1000
OffControlScanRate 60000

control

name id type engineering units Server Path Address opc
ControlTagRequest Request Integer sigyl sigyl.dk400.phases TA521_STIR.RQ N26:130
ControlTagCommand Command Integer sigyl sigyl.dk400.phases TA521_STIR.OC N21:13
ControlTagFailure Failure Integer sigyl sigyl.dk400.phases TA521_STIR.F N25:13
ControlTagOwner Owner Integer sigyl sigyl.dk400.phases TA521_STIR.W N27:13/3
ControlTagPause Pause Integer sigyl sigyl.dk400.phases TA521_STIR.P N27:13/4
ControlTagPaused Paused Integer sigyl sigyl.dk400.phases TA521_STIR.PD N27:13/5
ControlTagSingleStep SingleStep Integer sigyl sigyl.dk400.phases TA521_STIR.SS N27:13/2
ControlTagStatus Status Integer sigyl sigyl.dk400.phases TA521_STIR.ST N24:13
ControlTagStepIndex StepIndex Integer sigyl sigyl.dk400.phases TA521_STIR.SI N32:13
ControlTagUnit Unit Integer sigyl sigyl.dk400.phases TA521_STIR.UN N23:13

requests

none

parameters

name id type engineering units Server Path Address opc
SPEED 1 Integer RPM sigyl sigyl.dk400.phases TA521_STIR.P01 N102:58
STAGE_TIME 2 Integer SECONDS sigyl sigyl.dk400.phases TA521_STIR.P02 N102:59
ON_SECS 3 Integer SECONDS sigyl sigyl.dk400.phases TA521_STIR.P03 N102:60
OFF_SECS 4 Integer SECONDS sigyl sigyl.dk400.phases TA521_STIR.P04 N102:61
RECIRC 5 Enumeration sigyl sigyl.dk400.phases TA521_STIR.P05 N102:100

reports

name id type engineering units Server Path Address opc
ACTUAL_STAGE_TIME 1 Integer SECONDS sigyl sigyl.dk400.phases TA521_STIR.R01 N105:11

sequence

operations